• THS07 Temperature & Humidity Transmitter for Probe Type

THS07 Temperature & Humidity Transmitter for Probe Type

MOQ:20 PCS
Input : Capacitive Humidity Sensor & Pt100
Output : Temperature RTD(Pt100 / NTC10K);Humidity 0 ... 10 V;4 ... 20 mA
Accuracy : Temperature ±0.3°C+ 0.002°Cx tactual / Humidity(at +25°C) ±3%RH(30 ... 70%RH) of F.S. /
Humidity(at +15 ... 35°C) ±5%RH(20 ... 80%RH) of F.S.
Measuring range : Temperature 0 ... 50°C;Humidity 5 ... 95%RH
Model : THS07

● Compact design and easy to install
● An economical choice, high C/P ratio
● Industrial class sensor comes with high accuracy and long-term stability
Input
Signal connection
Capacitive Humidity Sensor & Pt100
Measuring range
Temperature:0 ... 50°C
Humidity:5 ... 95%RH
Recommended measuring range

Temperature:15 ... 35°C

Humidity:20 ... 80%RH


Output
Output
Temperature:RTD(Pt100 / NTC10K)
Humidity:0 ... 10 V;4 ... 20 mA
Signal connection
3-wire:Temp. / Humidity:(0 ... 10 V)
2-wire:Humidity:(4 ... 20 mA)
4-wire:Temperature
Temp. influence
0.2%RH/°C
Load resistance
0 ... 10 V;≧ 10 KΩ;4 ... 20 mA
RL<(+V-10) / 0.02<500 Ω
Output calibration(ZERO) adjustment degree
10% of zero-point and full-range
Response time(≧ 1m/s)
<20 s
Accuracy
Temperature
±0.3°C+ 0.002°Cx tactual
Humidity(at +25°C)
±3%RH(30 ... 70%RH) of F.S.
Humidity(at +15 ... 35°C)
±5%RH(20 ... 80%RH) of F.S.
Environment
Measuring medium
Air
Storage temperature
-5 ... +60°C
Max. flow speed
≦ 15 m/sec
Electrical
Power supply
3-wire:DC 24 V ±20%
2-wire:DC 9 ... 28 V
Current consumption
0 ... 10 V(3-wire):8 mA
4 ... 20 mA(2-wire):21 mA
Electric connection
PVC Cable0.32 mm2 x 6C
Installation
Fixed seat
Flange installation
Installation
Probe type
Protection
IP rating
IP24
Electric Protection
■ Polarity reversal protection
■ Over voltage
■ Short circuit
Certification
Certification
CE
Material
Housing
PC fire-proof class(UL94V-2)
Cable
PVC
Weight
17 g(Without cable)

The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect.
Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.


Monitoring for HVAC process / Air conditioning / Environmental ventilation control / Environmental monitoring for building / Factory / Clean / Room / Laboratory / Monitoring for storeroom / Crisper / Agriculture / Food industry / Temperature and humidity measuring in machinery or equipment