• PMM330 Differential Pressure Transmitter (Indoor)

PMM330 Differential Pressure Transmitter (Indoor)

Model : PMM330
Feature : Suitable for HVAC and light industry
Measuring element : Hot-wire type diff. pressure sensor, flow-through
Measuring range : ±50 ... ±1500 Pa
Output : 4 ... 20 mA / 0 ... 10 V / RS-485
Accuracy : ±1.5% F.S. ±3% M.V.
IP rating : IP65
  • Features
    ● Uses hot-wire type differential pressure sensor
    ● High sensitivity at low differential pressure, low zero-point drift, minimum measurable value as low as 1 Pa
    ● Pressure resistance up to 1 bar, differential pressure measurement range of ±50 ... ±1500 Pa
    ● Compact and easy to install
    ● Includes square root function for converting measurement into air velocity
    ● Provides analog output, optional RS-485 communication function
    ● DIP switch to adjust range and square root function

    The eyc-tech PMM330 differential pressure transmitter is designed for small differential pressures and low air velocities. It uses a hot-wire type differential pressure sensor with excellent zero-point stability and the ability to detect small differential pressures, allowing for precise measurements at low air velocities. The built-in square root function is used for converting measurement in to air velocity, and it provides flexible output
    options, making it an ideal choice for various differential pressure measurement applications.

  • Applications
    Environmental monitoring (Clean rooms, HVAC) / Differential pressure monitoring (Air ducts, filters) / Airflow monitoring
  • Download
  • Specification

    Measurement

    Measuring element
    Hot-wire type diff. pressure sensor, flow-through
    Measuring range
    ±50 ... ±1500 Pa

    Output

    Output
    4 ... 20 mA / 0 ... 10 V / RS-485
    Signal connection
    3-wire
    Load resistance
    Current output : ≦ 500 Ω
    Voltage output : ≧10 KΩ
    Response time
    t63 ≦ 2 ms
    Display type
    LCD Module with back light, double line character
    Display range
    Upon request, 2 decimal place (as unit is Pa : 1 decimal place)
    Digit height
    5.56 mm

    Accuracy (at 25°C)

    Accuracy
    ±1.5% F.S. ±3% M.V.
    Temperature influence
    1% m.v. per 10°C

    Environment

    Measuring medium
    Air
    Operating temperature
    0 ... 50°C
    Operating humidity
    0 ... 95%RH (Non-condensing)
    Storage temperature
    -20 ... +60°C

    Electrical

    Power supply
    DC 24 V ±10% & AC 24 V ±10%
    Current consumption
    DC 24 V : ≦45 mA (Display) / ≦40 mA(Non-display)
    AC 24 V : ≦95 mA (Display) / ≦90 mA(Non-display)
    Overvoltage protection
    ≦DC 40 V
    Electrical connection
    M type ( M12 - 4 PIN connector ) / ( M12 - 5 PIN connector )
    N type ( M16 plastic cable gland ) 
    *M type with 2 m cable

    Installation

    Installation
    Indoor wall type

    Protection

    IP rating
    IP65
    Electrical protection
    ■ Over-voltage
    ■ Reverse polarity
    ■ Short circuit
    Pressure resistance
    1 bar
    Burst pressure
    3 bar

    Certification

    Certification
    CE

    Material

    Housing
    PC fire-proof class(PC-110)(UL94V-2)
    Weight
    Display : 152 g
    Non-display : 127 g
Note : Design and specifications are subject to change without notice.
Note : If the product has RS-485 function, to avoid damaging product, please make sure the product and the device which connect with RS-485 are on common ground.