FTC06 Temperature and Flow Transmitter
Model :
FTC06
Features : Thermal mass measurement of flow and temperature with RS-485, ideal for continuous liquid cooling monitoring in data centers.
Sensor type : PT sensor
Measuring range : 0 ... 3 m/s (Water), 0 ... 60 m/s (Air)
Output : 4 ... 20 mA / RS-485 / NPN
Repeatability : ±0.5%
Accuracy : Water ±(1% mv + 0.05 m/s), Air ±(1% mv + 0.5 m/s)
IP rating : IP65, IP67 (Option)
Sensor type : PT sensor
Measuring range : 0 ... 3 m/s (Water), 0 ... 60 m/s (Air)
Output : 4 ... 20 mA / RS-485 / NPN
Repeatability : ±0.5%
Accuracy : Water ±(1% mv + 0.05 m/s), Air ±(1% mv + 0.5 m/s)
IP rating : IP65, IP67 (Option)
-
Features● Rugged aluminum housing for harsh environments.
● Thermal mass measurement with fast response and low pressure loss.
● RS-485 output for real-time flow and temperature.
● Works with eyc-tech DPM04 for instantaneous and totalized flow display.
● Tracks flow changes for early anomaly detection and preventive maintenance.
● Optimizes cooling efficiency and supports ESG energy savings.
● One-piece probe design for stable long-term liquid cooling measurement. -
ApplicationsAI Servers / Precision Manufacturing / Data Centers / Semiconductor / Electronics / Chemical / Pharmaceutical / Steel industry / Biotechnology / Industrial process monitoring / Air conditioning / Cleanroom / Laboratory / Weather station / Hospital / Buildings / Dryers / Factories / Storage rooms / Environmental ventilation control / Environmental test chambers / Greenhouses
-
Download
-
Specification
Input
Input
PT sensor
Measuring range
0 ... 3 m/s (Water)
0 ... 60 m/s (Air)
Output
Output
4 ... 20 mA / RS-485 / NPN
Load resistance
Current output:≦500 Ω
Response time (at +25°C)
t90 <10 sec
Filter response
0 ... 100 adjustable
Sampling time
1 cycle/sec
Accuracy (at +25 °C)
Repeatability
±0.5%
Water flow
0 ... 1 m/s:±( 1% of mv. + 0.05 m/s )
1 ... 2 m/s:±( 2% of mv. + 0.2 m/s )
2 ... 3 m/s:±( 3% of mv. + 0.3 m/s )
Air flow
0 ... 30 m/s:±( 1% of mv. + 0.5 m/s )
30 ... 60 m/s:±( 1.5% of mv. + 1 m/s )
Temperature
±0.5% of F.S
Temperature drift
≦0.5% F.S. / °C
Installation angle effect
<1.5 % mv for α <10°
Uncertainty of factory calibration
±1%
*The measurement range is defined at the standard condition(1013 mbar, 25°C).*mv = measured value*At an air velocity of 0 m/s, self-heating of the probe may affect the temperature reading in air.Therefore, the measured value may not represent the actual ambient temperature.*CAUTION: The probe may become hot during operation. To prevent burns, do not touch theprobe directly.Communication
Comm. Interface & Protocol
RS-485 Modbus RTU
RS-485 Baud Rate
9600、19200、38400、57600、115200 bps
Electrical
Power supply
DC 24 V ±10%
Current consumption
< 120 mA
Electrical connector
M12 8P connector
Environmental
Medium
Liquid, air
Operating Temp. (Housing)
-20 ... +60°C
Operating Humid. (Housing)
0 ... 90% (Non-condensing)
Probe Operating Temp.
0 ... 50°C
Storage temperature
-25 ... +60°C
Probe pressure resistance
16 bar
Installation
Installation
1/4″G or 1/2″G thread
Certification
Certification
CE
Protection
IP rating
IP65
Electrical protection
■ Reverse polarity ■ Over-voltage
Material
Housing
Aluminum alloy
Probe
316L
Weight
1/4″G thread : 85 g
1/2″G thread : 105 g
Note : Design and specifications are subject to change without notice.
Note : If the product has RS-485 function, to avoid damaging product, please make sure the product and the device which connect with RS-485 are on common ground.