• FTC06 Temperature and Flow Transmitter
  • FTC06 Temperature and Flow Transmitter

FTC06 Temperature and Flow Transmitter

Model : FTC06
Features : Thermal mass measurement of flow and temperature with RS-485, ideal for continuous liquid cooling monitoring in data centers.
Sensor type : PT sensor
Measuring range : 0 ... 3 m/s (Water), 0 ... 60 m/s (Air)
Output : 4 ... 20 mA / RS-485 / NPN
Repeatability : ±0.5%
Accuracy : Water ±(1% mv + 0.05 m/s), Air ±(1% mv + 0.5 m/s)
IP rating : IP65, IP67 (Option)
  • Features
    ● Rugged aluminum housing for harsh environments.
    ● Thermal mass measurement with fast response and low pressure loss.
    ● RS-485 output for real-time flow and temperature.
    ● Works with eyc-tech DPM04 for instantaneous and totalized flow display.
    ● Tracks flow changes for early anomaly detection and preventive maintenance.
    ● Optimizes cooling efficiency and supports ESG energy savings.
    ● One-piece probe design for stable long-term liquid cooling measurement.
  • Applications
    AI Servers / Precision Manufacturing / Data Centers / Semiconductor / Electronics / Chemical / Pharmaceutical / Steel industry / Biotechnology / Industrial process monitoring / Air conditioning / Cleanroom / Laboratory / Weather station / Hospital / Buildings / Dryers / Factories / Storage rooms / Environmental ventilation control / Environmental test chambers / Greenhouses
  • Download
  • Specification

    Input

    Input
    PT sensor
    Measuring range
    0 ... 3 m/s (Water)
    0 ... 60 m/s (Air)

    Output

    Output
    4 ... 20 mA / RS-485 / NPN
    Load resistance
    Current output:≦500 Ω
    Response time (at +25°C)
    t90 <10 sec
    Filter response
    0 ... 100 adjustable
    Sampling time
    1 cycle/sec

    Accuracy (at +25 °C)

    Repeatability
    ±0.5%
    Water flow
    0 ... 1 m/s:±( 1% of mv. + 0.05 m/s )
    1 ... 2 m/s:±( 2% of mv. + 0.2 m/s )
    2 ... 3 m/s:±( 3% of mv. + 0.3 m/s )
    Air flow
    0 ... 30 m/s:±( 1% of mv. + 0.5 m/s )
    30 ... 60 m/s:±( 1.5% of mv. + 1 m/s )
    Temperature
    ±0.5% of F.S
    Temperature drift
    ≦0.5% F.S. / °C
    Installation angle effect
    <1.5 % mv for α <10°
    Uncertainty of factory calibration
    ±1%
    *The measurement range is defined at the standard condition(1013 mbar, 25°C).
    *mv = measured value
    *At an air velocity of 0 m/s, self-heating of the probe may affect the temperature reading in air.
    Therefore, the measured value may not represent the actual ambient temperature.
    *CAUTION: The probe may become hot during operation. To prevent burns, do not touch the
    probe directly.

    Communication

    Comm. Interface & Protocol
    RS-485 Modbus RTU
    RS-485 Baud Rate
    9600、19200、38400、57600、115200 bps

    Electrical

    Power supply
    DC 24 V ±10%
    Current consumption
    < 120 mA
    Electrical connector
    M12 8P connector

    Environmental

    Medium
    Liquid, air
    Operating Temp. (Housing)
    -20 ... +60°C
    Operating Humid. (Housing)
    0 ... 90% (Non-condensing)
    Probe Operating Temp.
    0 ... 50°C
    Storage temperature
    -25 ... +60°C
    Probe pressure resistance
    16 bar

    Installation

    Installation
    1/4″G or 1/2″G thread

    Certification

    Certification
    CE

    Protection

    IP rating
    IP65
    Electrical protection
    ■ Reverse polarity ■ Over-voltage

    Material

    Housing
    Aluminum alloy
    Probe
    316L
    Weight
    1/4″G thread : 85 g
    1/2″G thread : 105 g
Note : Design and specifications are subject to change without notice.
Note : If the product has RS-485 function, to avoid damaging product, please make sure the product and the device which connect with RS-485 are on common ground.