• eYc TP04 Temperature Transmitter (2-wire for duct type)

eYc TP04 Temperature Transmitter (2-wire for duct type)

Input : RTD Pt100 Ω
Output : DC 4 ... 20 mA((2-wire)
Accuracy : ±0.5% of F.S.
Power supply : DC 10 ... 30 V
IP rating : IP65
●YUDEN-TECH CO.,LTD. Calibration Laboratory - ( ILAC / TAF ) Test report, for more detailed information please contact us.
(TAF accreditation:3032, complying with ISO / IEC 17025 ) TAF has mutual recognition arrangement with ILAC MRA
Model : eYc TP04

SS Housing, all-in design with anti-condensation function and good heat dissipation
Good measuring repeatability and anti-interference
Monitoring for long-distance temperature signal transmission
Signal transfer from PT sensor to 4 ... 20 mA
With SD05 integrated signal indicator for local display(Optional)

More potential product articles, welcome to visit the link below
eYc-Success-StoryeYc-FAQ

Input
Input : RTD Pt100 Ω
Pt100 Ω sensor current : <0.8 mA
ZERO adjustment range : ±10%
SPAN adjustment range : ±10%

Output
Output : DC 4 ... 20 mA((2-wire)
Accuracy : ±0.5% of F.S.
Load resistance : ≦ (Supply voltage - 8 V) / 0.02A Ω
Power stability : ±0.025% / V
Temperature drift : <± 0.015%F.S. / °C
Calibration temperature : 20 ... 28°C
Response time : < 250 ms

Electrical
Power supply : DC 10 ... 30 V
Electrical connector : DIN 43650 ABS

Environment
Medium : Air
Operating Temp. : -20 ... 80°C
Operating humidity : 100%RH (Non-condensing)

Protection
Pt100Ω signal disconnection protection & output : >23 mA
Pt100Ω signal short circuit protection & output : <3 mA
Output polarity protection : Yes
IP rating : IP65

Certification
Certification : CE

Material
Housing : SUS304
Weight : 50 mm:250 g / 200 mm:260 g

Option
Sleeve pipe / Size : 30 / 80 / 130 / 180 mm R1/2″sleeve

The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect.
Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.


For industries in heating / Ventilation / Air conditioning / Cooling / Water power / Electricity, etc. / For process in agriculture / Green house / Environmental engineering / Food / Pharmaceutical industry / Machinery manufacturing / Storage tank / Compressor / Hydraulic equipment