• TP02 Temperature Transmitter for DIN-rail Type

TP02 Temperature Transmitter for DIN-rail Type

Model : TP02
Features:Compact size. Easy to install. Cost effective.
Sensor type:RTD Pt100(3-wire)
Measuring range:-50 ... 200°C
Output:DC 4 ... 20 mA(2-wire)
Accuracy:±0.1% F.S.
IP rating:IP30(Housing) / IP10(Terminal)
  • Features
    ● Special IC for RTD;High accuracy is assured
    ● TP02 with smaller volume so lesser space for installation is required
    ● High quality and low price
    ● DIN-rail type;Quick to install

  • Applications
    Monitoring for long-distance temperature signal transmission / For industries in heating / Ventilation / Air conditioning / Cooling / Water power / Electricity, etc. / For process in agriculture / Green house / Environmental engineering / Food / Pharmaceutical industry
  • Download
  • Specification
    Input
    Input signal:RTD Pt100(3-wire)
    Cable resistance:≦50 Ω(3 wires with the same resistance)
    Pt100 sensor current:<0.8 mA
    ZERO adjustment range:±10%
    SPAN adjustment range:±10%

    Output
    Output signal:DC 4 ... 20 mA(2-wire)
    Load resistance:≦(Supply voltage - 8 V) / 0.02A Ω
    Load resistance stability:±0.05% / 100Ω
    Power stability:±0.025% / V 

    Accuracy
    Accuracy:±0.1% of F.S.

    Temperature
    Temperature drift:<±0.015% F.S. / °C 
    Calibration temperature :20 ... 28°C
    Response time:<250 ms

    Environment
    Medium:Air
    Operating temperature:-20 ... 60°C
    Operating humidity:0 ... 95%RH(Non-condensing)

    Electrical specification
    Power supply:DC 10 ... 30 V
    Operating environment:-20 ... 60°C / 0 ... 95%RH(Non-condensing)

    Protection
    Pt100 signal disconnection protection & output:>23 mA
    Pt100 signal short circuit protection & output:<3 mA
    Output polarity protection:Yes
    IP rating:Housing:IP30 / Terminal:IP10

    Certification
    Certification:CE

    Material
    Housing:ABS(UL94V-0)
Note : Design and specifications are subject to change without notice.