TP02 Temperature Transmitter for DIN-rail Type
Model :
TP02
Features:Compact size. Easy to install. Cost effective.
Sensor type:RTD Pt100(3-wire)
Measuring range:-50 ... 200°C
Output:DC 4 ... 20 mA(2-wire)
Accuracy:±0.1% F.S.
IP rating:IP30(Housing) / IP10(Terminal)
Sensor type:RTD Pt100(3-wire)
Measuring range:-50 ... 200°C
Output:DC 4 ... 20 mA(2-wire)
Accuracy:±0.1% F.S.
IP rating:IP30(Housing) / IP10(Terminal)
-
Features● Special IC for RTD;High accuracy is assured
● TP02 with smaller volume so lesser space for installation is required
● High quality and low price
● DIN-rail type;Quick to install
-
ApplicationsMonitoring for long-distance temperature signal transmission / For industries in heating / Ventilation / Air conditioning / Cooling / Water power / Electricity, etc. / For process in agriculture / Green house / Environmental engineering / Food / Pharmaceutical industry
-
Download
-
SpecificationInput
Input signal:RTD Pt100(3-wire)
Cable resistance:≦50 Ω(3 wires with the same resistance)
Pt100 sensor current:<0.8 mA
ZERO adjustment range:±10%
SPAN adjustment range:±10%
Output
Output signal:DC 4 ... 20 mA(2-wire)
Load resistance:≦(Supply voltage - 8 V) / 0.02A Ω
Load resistance stability:±0.05% / 100Ω
Power stability:±0.025% / V
Accuracy
Accuracy:±0.1% of F.S.
Temperature
Temperature drift:<±0.015% F.S. / °C
Calibration temperature :20 ... 28°C
Response time:<250 ms
Environment
Medium:Air
Operating temperature:-20 ... 60°C
Operating humidity:0 ... 95%RH(Non-condensing)
Electrical specification
Power supply:DC 10 ... 30 V
Operating environment:-20 ... 60°C / 0 ... 95%RH(Non-condensing)
Protection
Pt100 signal disconnection protection & output:>23 mA
Pt100 signal short circuit protection & output:<3 mA
Output polarity protection:Yes
IP rating:Housing:IP30 / Terminal:IP10
Certification
Certification:CE
Material
Housing:ABS(UL94V-0)
Note : Design and specifications are subject to change without notice.
Note : If the product has RS-485 function, to avoid damaging product, please make sure the product and the device which connect with RS-485 are on common ground.