• eYc TGP03/THP03 Multifunction CO2/PM2.5 Indoor Air Quality Monitor

eYc TGP03/THP03 Multifunction CO2/PM2.5 Indoor Air Quality Monitor

Features : Real-Time Data of PM2.5, CO2, temperature & humidity. / Anti-condensation and nicer long-term stability.
Input : Temperature MEMS / Humidity MEMS / CO2 NDIR / PM2.5 Infrared LED
Output : RS-485
Accuracy : Temperature ± 0.5 °C / Humidity ± 5 %RH ( at 30 ... 80 %RH ) /
CO2 ± 40 PPM ± 3 % of Reading / PM2.5 ± 10 μg/m3 ± 5% of Reading
Measuring Range : Temperature 0 ... 50 °C / Humidity 0 ... 100 %RH (Non-condensing) /
CO2 0 ... 2000 PPM / PM2.5 0 ... 500 μg/m3
Display : Optional
Model : eYc TGP03THP03

eYc TGP03, PM2.5 multifunction 4-in-1 air quality monitor, which is specially used to monitor 4 kinds of physical quantities as PM2.5, CO2 (carbon dioxide), temperature and humidity.
There are 3 types of excellent sensors in this monitor such as MEMS, NDIR, and Infrared LED. 
That is why we have the nicer Long-term stability of measuring and react quickly.
TGP03 is easy to install and featured with compact size and elegant outlook, and also provide programmable software to monitor and record the data via RS-485.

Stealthy Fatal Killer PM2.5 exist in the ambient. It threatens human health 
if the value of PM2.5 and CO2 excess the standard 35μg/m3 and 1000 PPM.

More potential product articles, welcome to visit the link below
eYc-Success-StoryeYc-FAQ
Measuring range 
Temp.:0 ... 50℃
Humidity:0 ... 100%RH  (Non-condensing)
CO2:0 ... 2000 ppm
PM2.5:0 ... 500 ㎍/m3
Accuracy
Temp.:±0.5℃
Humidity:± 5 % RH ( at 30 ... 80%RH)
CO2:±40 PPM ± 3 % of Reading
PM2.5:± 10 ㎍/m3, ±5% of Reading
Output
Signal output:RS-485
Protocol:Protocol
Signal connection
3-wire
Power supply
AC : 24 ± 10 %;DC : 12 …36V
Protection rating
IP20

*Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.

The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.
● Indoor air quaility
● Public and interior place such as restaurant, department store,  museum, library and so on
HVAC / Air ventilation system / Library / Green house / Department store / Data station / Storehouse and so on