• eYc TGP03 Multifunction PM2.5 Indoor Air Quality Monitor

TGP03 Multifunction CO2/PM2.5 Indoor Air Quality Monitor

Model : TGP03
Features:Suitable for HVAC application. Simple appearance. Multi-measurement.
Sensor type:Temperature & Humidity MEMS / CO2 NDIR / PM2.5 Infrared LED
Measuring range:0 ... 50 °C / 0 ... 100 %RH (Non-condensing ) / 0 ... 2000 PPM / PM2.5 0 ... 500 μg/m3
Output:RS-485
Accuracy:±0.5°C / ±5% RH / ±40 PPM ±3% of reading / ± 10 μg/m3 ± 5% of reading
IP rating:IP20
  • Features
    【4-in-1】Real-Time Data of PM2.5, CO2, temperature & humidity
    【Real-time data monitoring】Quickly monitor and LCD display
    【Nicer stability】NDIR,MEMS , and Infrared LED sensor
    【Sensor protected】Anti-condensation and nicer long-term stability
    【Operate easy】Remote monitoring data via Modbus RS-485 digital output
    【Install Quickly】Compact size and elegant outlook and easy to install on the wall
    【Data logger software】Free programmable software to monitor and record local data via RS-485

    Stealthy Fatal Killer PM2.5 exist in the ambient. It threatens human health if the value of PM2.5 and CO2 excess the standard 35μg/m3 and 1000 PPM.

  • Applications
    Indoor air quaility / Public and interior place such as restaurant, department store, museum, library and so on / HVAC / Air ventilation system / Library / Green house / Department store / Data station / Storehouse and so on
  • Download
  • Specification
    Display
    Display:LCD module without backlight
    Display readout:Double line character (Up:Temperature;Down:Humidity)
    Digit:PM2.5:3 digits and 1 decimal / CO2 :4 digits / T&H:3 digits & 1 decimal
    Digit height:17.91 mm

    Input
    Temperature:MEMS sensor 
    Humidity:MEMS sensor 
    CO2NDIR sensor
    PM2.5:Infrared LED

    Measuring range
    Temperature0 ... 50°C
    Humidity00 ... 100%RH (Non-condensing)
    CO20 ... 2000 PPM 
    PM2.50 ... 500 μg/m3

    Output
    Output:RS-485
    Protocol:Protocol
    Interface:Modbus RTU
    Address:1 ... 247
    Baud Rate:9600, 19200, 38400, 57600, 115200

    Warm-up time
    Temp. & Humidity:< 2 min.,stable time 20 mins.
    CO2< 2 min.,stable time 20 mins.

    Response time
    Temp. & Humidity:t 63(15 ... 45°C / 33 ... 75%RH) ≦ 10 sec 
    CO2t 90 < 2 min.
    PM2.5:3 sec

    Sampling time
    Temp. & Humidity:About 3 sec
    CO2About 6 sec
    PM2.5About 20 sec 

    Accuracy
    Temperature:±0.5°C
    Humidity:±5%RH (at 30 ... 80%RH)
    CO2±40 PPM±3% of reading
    PM2.5±10 μg/m3 ±5% of reading

    Electrical
    Medium:Air
    Operating environment:0 ... 50°C / 0 ... 100%RH (Non-condensing)
    Operating environment (CO2):0 ... 50°C / 0 ... 85%RH
    Storage temperature:-20 ... + 60°C

    Electrical
    Power supply:DC 24 V±10% & AC 24 V±10%
    Current consumption:DC 24 V:20 mA /AC 24 V:35 mA
    Starting current:DC 24 V:94 mA /AC 24 V:158 mA
    Electrical connection:4P connector

    Installation
    Installation:Indoor and wall mount

    Protection
    IP rating:IP20
    Electrical protection:■Polarity protection ■Short-circuit

    Certification
    Certification:CE

    Material
    Housing:PC (PC - 110)(UL94V-2)
    Weight:115 g (Display / 100 g (Without display)
Note : Design and specifications are subject to change without notice.
Note : If the product has RS-485 function, to avoid damaging product, please make sure the product and the device which connect with RS-485 are on common ground.