• PMD330 Differential Pressure Transmitter (Indoor)

PMD330 Differential Pressure Transmitter (Indoor)

Model : PMD330
Features : Suitable for hospital and clean room; Wide measuring range
Measuring element : Piezoresistive diff. pressure sensor, no flow-through
Measuring range:±50 ... ±10000 pa
Output : 4 ... 20 mA / 0 ... 10 V / RS-485
Accuracy : ±2.0% F.S.
IP rating : IP65
  • Features
    ● Uses piezoresistive differential pressure sensor
    ● No flow-through structure, pressure ports are not interconnected
    ● Differential pressure measurement range of ±50 ... ±10,000 Pa
    ● Compact and easy to install
    ● Includes square root function for converting into air velocity
    ● Provides analog output, optional RS-485 communication function
    ● DIP switch to adjust range and square root function

    The eyc-tech PMD330 differential pressure transmitter (Indoor) is designed for indoor environmental monitoring. It uses a piezoresistive differential pressure sensor with a no flow through structure. The built-in square root function is used for converting into air velocity, and it provides flexible output options to meet the needs of different scenarios. Users can easily configure it using the DIP switch, making it an ideal choice for various differential pressure measurement applications.

  • Applications
    Environmental monitoring (HVAC, clean rooms, hospitals) / Differential pressure monitoring (air ducts, filters) / Airflow monitoring
  • Download
  • Specification

    Measurement

    Measuring element
    Piezoresistive diff. pressure sensor, no flow-through
    Measuring range
    ±50 ... ±10000 pa

    Output

    Output
    4 ... 20 mA / 0 ... 10 V / RS-485
    Signal connection
    3-wire
    Load resistance
    Current output : ≦ 500 Ω
    Voltage output : ≧10 KΩ
    Response time
    t63 ≦ 2 ms
    Display type
    LCD Module with back light, double line character
    Display range
    Upon request, 2 decimal place (as unit is Pa : 1 decimal place)
    Digit height
    5.56 mm

    Accuracy

    Accuracy
    ±2.0% of F.S.
    Temperature influence
    ±1.75%

    Environment

    Measuring medium
    Air
    Operating temperature
    0 ... 50°C
    Operating humidity
    0 ... 95%RH (Non-condensing)
    Storage temperature
    -20 ... +60°C

    Electrical

    Power supply
    DC 24 V ± 10 % & AC 24 V ± 10 %
    Current consumption
    DC 24 V : ≦45 mA(Display) / ≦40 mA(Non-display)
    AC 24 V : ≦95 mA(Display) / ≦90 mA(Non-display)
    Overvoltage protection
    ≦DC 40 V
    Electrical connection
    M type ( M12 - 4 PIN connector ) / ( M12 - 5 PIN connector )
    N type ( M16 plastic cable gland ) 
    *M type with 2 m cable

    Installation

    Installation
    Indoor wall type

    Protection

    IP rating
    IP65
    Electrical protection
    ■ Over-voltage
    ■ Reverse polarity
    ■ Short circuit
    Pressure resistance
    ±50 ... ±500 pa : 0.25 bar
    ±1000 ... ±10000 pa : 0.5 bar
    Burst pressure
    ±50 ... ±2500 pa : 0.75 bar
    ±5000 ... ±10000 pa : 1.25 bar

    Certification

    Certification
    CE

    Material

    Housing
    PC fire-proof class(PC-110)(UL94V-2)
    Weight
    Display : 152 g
    Non-display : 127 g
Note : Design and specifications are subject to change without notice.
Note : If the product has RS-485 function, to avoid damaging product, please make sure the product and the device which connect with RS-485 are on common ground.