Model : PHD330
Features:Suitable for industrial application. Wide measuring range.
Sensor type:Piezoelectric differential pressure module
Measuring range:±50 ... ±10000 pa
Output:4 ... 20 mA / 0 ... 10 V
Accuracy:±2.0% F.S.
IP rating:IP65
  • Features
    ● Silicon chips on differential pressure module of MEMS integration technology
    ● Offset function / UI software
    ● Low-pressure monitoring, high pressure resistance
    ● RS-485 communication interface(Optional), Modbus RTU protocol
    ● Physical unit switch(User Interface):mbar / Pa / hPa / kPa / mmH2O / mmWS / inH2O / mmHg
    ● Square root function
  • Applications
    Exhaust emission / Environmental engineering / Air duct / Filter / Monitor differential pressure and environment air flow
  • Download
  • Specification
    Input
    Input type:Piezoelectric differential pressure module
    Measuring range:±50 ... ±10000 pa

    Output
    Output:4 ... 20 mA / 0 ... 10 V
    Signal connection:3-wire
    Modbus:RS-485
    Load resistance(Current output):4 ... 20 mA<500 Ω / 0 ... 10 V≧100 KΩ
    Response time(t63):≦2 ms
    Display type:LCD Module with back light, double line character
    Display range:V=Air velocity(at 25°C) / Q=Air quantity(with eYc AFMT)
    Digit height:5.56 mm

    Environment
    Measuring medium:Air
    Operating temperature:-20 ... +80°C(Non-display) / 0 ... +50°C(Display)
    Operating humidity:0 ... 95%RH(Non-condensing)
    Storage temperature:-40 ... +80°C

    Accuracy
    Accuracy:±2.0% F.S.
    Temperature influence:±1.75%(5 ... 55°C)

    Electrical
    Power supply:AC 24 V ±10% / DC 24 V ±10%
    Current consumption:DC 24 V:≦45 mA(Display) / ≦40 mA(Non-display), AC 24 V:≦95 mA(Display) / ≦90 mA(Non-display)
    Overvoltage protection:≦DC 40 V
    Electrical connection:M12 connector

    Installation
    Installation:Wall

    Protection
    IP rating:IP65
    Electrical protection:■ Polarity protection ■ Over-voltage ■ Short circuit
    Pressure resistance:±50 ... ±500 pa:0.25 bar / ±1000 ... ±10000 pa:0.5 bar
    Burst pressure:±50 ... ±2500 pa:0.75 bar / ±5000 ... ±10000 pa:1.25 bar

    Certification
    Certification:CE

    Material
    Housing:Aluminum alloy
    Weight:Display:497 g;Non-display:478 g
Note : Design and specifications are subject to change without notice.
Note : If the product has RS-485 function, to avoid damaging product, please make sure the product and the device which connect with RS-485 are on common ground.