• FTS140 Hot Wire Air Velocity Transmitter

FTS140 Hot Wire Air Velocity Transmitter

Model : FTS140
Features : Economic model for HVAC application.
Sensor type : Hot wire mass flow transmitter
Measuring range : 0 ... 20 m/s
Output : 4 ... 20 mA / DC 0 ... 10 V
Accuracy : ±3% F.S.
IP rating : IP54
  • Features
    Using Mass flow principle A better choice for HVAC engineering

    ● Hot wire mass flow transmitter
    ● IP rating : IP54
    ● Linear adjustment function
    ● Switching analog output by dip switch
    ● The housing and probe material are PC fire-proof

    FTS140 hot wire air velocity transmitter, using mass flow measuring principle, stable electrical bridge with good accuracy, simple structure, stable performance and low flow sensitivity.
    It is suitable for use in HVAC air conditioning environment measurement, optimization and adjustment of system performance, ventilation control.
    Duct type, easy installation, suitable is used extensively in environmental engineering projects, as facility and factory maintenance.
  • Applications
    Monitoring air and flow for industrial process / HVAC / Building / Factory
  • Download
  • Specification

    Input

    Sensor
    Hot wire mass flow transmitter
    Measuring range
    0 ... 20 m/s
    Min. measuring range
    0.2 m/s
    Installation angle effect
    (When the installation angle<10°) ±3%F.S.(Nonlinear error, Hysteresis)

    Output

    Output signal
    4 ... 20 mA / DC 0 ... 10 V
    Signal connection
    3-Wire
    Load resistance
    Current output : ≦500 Ω
    Voltage output : ≧10 KΩ
    Response time
    t90≦5 sec(τ : 90%)

    Accuracy

    Accuracy
    ±3%F.S.
    Temp. influence
    0.3% / °C

    Environment

    Medium & Temp.
    Air, 0 ... 50°C
    Body operating Temp.
    0 ... 50°C
    Body operating Humid.
    95%RH(Non-condensing
    Storage Temp.
    -20 ... +60°C

    Electrical

    Power supply
    DC 24 V & AC 12 ... 30 V
    Current consumption
    DC 24 V : 120 mA / AC 12 V : 350 mA / AC 24 V : 180 mA
    Overvoltage protection
    DC : <40 V;AC : <40 V
    Electrical connection
    Terminal

    Installation

    Fixed seat
    Duct type / Flange type

    Protection

    IP rating
    IP54
    Electrical protection
    ■ Reverse polarity
    ■ Over-voltage
    ■ Short-circuit

    Certification

    Certification
    CE

    Material

    Housing / Probe
    PC fire-proof(UL94V-2) / PC fire-proof
    Probe head / Wire
    PC
    Weight
    ~150 g
Note : Design and specifications are subject to change without notice.