THM06 Industrial Temperature and Humidity Transmitter
Sensor type : Capacitive Humidity Sensor & Pt 100
Measuring range : -40 ... +180℃
Output : 4 ... 20 mA / 0 ... 10 V / RS-485
Accuracy : Temperature ±0.15°C / Humidity ±2%RH
IP rating : IP67
-
Features
Adaptation to high temperature and high humidity conditions or harsh environments such as chemical pollution & condensation
Each physical quantity measuring range is calculated by converting the temperature and humidity of the product. The values are for reference only.
● IP67, Stainless steel SUS304, Pressure resistance 16 bar
● 330° rotatable, lightweight, unrestricted installation
● Optional on-site real-time display
● Process temperature up to 180°C, custom up to 200°C (Optional)
● Output : Analog / RS-485
● Wide measurement range, Temp. : -40 ... +180°C, Humidity : 0 ... 100%RH
● Measuring parameter : relative humidity, dew point temperature, frost point temperature, wet bulb temperature, water vapor partial pressure, mixing ratio, absolute humidity and enthalpy.
THM06 has a sturdy outer housing and a wide range of applications. It is also suitable for use in harsh environmental conditions.
Capacitive sensor, high accuracy of temperature, and humidity measurement, fast response, fast recovery after condensation.
It is stability even in long-term high humidity, also it has temperature compensation and computer linear calibration temperature and humidity function, suitable for industrial process gas supply or consumption, compressed dry air flow, and consumption monitoring. -
ApplicationsSemiconductor / Electronics / Steel industry / Chemical / Pharmaceutical / Biotechnology industry / Tobacco industry / Industrial process control (drying or humidification) / Environmentally controlled / High humidity storage / Food
-
Download
-
SpecificationInput
Signal type : Capacitive humidity sensor & Pt100
Temperature range : -40°C ... +180°C, Customized up to 200°C (Optional)
Humidity range : 0 ... 100%RH (non-condensing)
(Please refer tophysical quantity measuring range list)
Output
Signal : 4 ... 20 mA / 0 ... 10 V / RS-485
Signal connection : 3-wire
Accuracy
Temperature : ±0.15°C+0.002°C x tactual
Humidity (0 ... 90%) : Nonlinear error:±1.2%RH, Hysteresis error:±0.8%RH, Repeatability error:±0.4%RH
Humidity (90 ... 100%) : ±2%RH
Reaction time t90 (at +25°C) : <20 sec (S.S. metal grid filter with mesh), <30 sec (Sintered filter)
Load resistance : Current output:≦ 500 Ω, Voltage output:≧ 100 KΩ
Electrical
Power supply : DC 24 V±10%
Current consumption : DC 24 V:60 mA
Electrical connections : M12 connector
Environmental
Medium : Air, or medium compatible with stainless steel
Temp. Operating : -20 ... +60°C (Body);-40 ... +180°C (Probe)
Humid. Operating : 0 ... 90%RH (Body, non-condensing)
Probe pressure : 16 bar
Storage temperature : -20 ... +60°C
Installation
Installation : 1/2" PT movable thread
Protection
IP rating : IP67
Electrical protection : ■Reverse polarity ■Over-voltage ■Short-circuit
Material
Housing : SUS304
Weight : Metal:318 g (without wire)