TP01 + Temperature Probe | Smart Building Cooling Tower Energy-Saving Solution
Background Introduction
Based on practical experience, when a chiller operates under full-load conditions, with cooling water temperature at 30/35°C and chilled water temperature at 12/7°C, a 1°C increase or decrease in cooling water temperature may cause the chiller’s power consumption to increase or decrease by approximately 3%. Therefore, properly lowering the cooling water temperature can help reduce the power consumption of the chiller. However, if the cooling water temperature is too low, it may negatively affect the chiller’s power consumption. As a result, properly controlling the cooling water temperature to avoid excessively low condensing temperature and reduced chiller efficiency is very important.
The outlet water temperature of a cooling tower is mainly affected by the heat exchange performance of the cooling fins, the uniformity of water distribution, the cooling airflow volume, and the wet-bulb temperature of the air entering the cooling tower. When the system capacity is appropriate and maintenance is properly performed, the main factors affecting the cooling tower outlet water temperature are reduced to two key parameters:
- Cooling airflow volume of the cooling tower
- Wet-bulb temperature of the air entering the cooling tower
Therefore, controlling these two parameters to create the most favorable operating conditions for the cooling tower is the key to energy savings.
By using the outdoor wet-bulb temperature together with an inverter to control the fan speed of the cooling tower, the cooling tower fan can operate at the most suitable speed. This prevents unnecessary fan power consumption while maintaining the operating efficiency of the chiller, thereby achieving effective energy savings.
Solution
The solution mainly uses the outdoor wet-bulb temperature together with an inverter to control the fan speed of the cooling tower, allowing the cooling tower fan to operate at the most suitable speed. This helps reduce the power consumption of the cooling tower fan while maintaining the operating efficiency of the chiller, achieving effective energy savings. All data can also be converted through an RS-485 converter board and transmitted to the cloud for data logging.
The TP01 two-wire large-head temperature transmitter, used together with an eyc-tech temperature probe, is installed on the inlet and outlet water pipes of the cooling tower. By measuring the inlet and outlet water temperatures, it controls the frequency of the downstream inverter to achieve energy-saving operation. All data can also be converted through an RS-485 converter board and transmitted via RS-485 to the cloud for data logging.
In addition, the THM80X series or THS30X series temperature and humidity transmitters can be installed near the cooling tower or inside the electrical control panel to measure the wet-bulb temperature, supporting real-time monitoring of measurement data.