TP02 Temperature Transmitter for DIN-rail Type
Features : Compact size. Easy to install. Cost effective.
Sensor type : RTD Pt100(3-wire)
Measuring range : -50 ... 200°C
Output : DC 4 ... 20 mA(2-wire)
Accuracy : ±0.1% F.S.
IP rating : IP30(Housing) / IP10(Terminal)
Features
● Temperature range : -50 ... 200°C
● Special IC for RTD;High accuracy is assured
● TP02 with smaller volume so lesser space for installation is required
● High quality and low price
● DIN-rail type;Quick to install
Specification
Input | |
Input signal | RTD Pt100 Ω (3-wire) |
Cable resistance | ≦50 Ω (3 wires with the same resistance) |
PT100Ω sensor current | <0.8 mA |
ZERO adjustment range | ±10% |
SPAN adjustment range | ±10% |
Output | |
Signal | DC 4 ... 20 mA (2-wire) |
Load resistance | ≦(Supply voltage - 8 V) / 0.02 A Ω |
Load resistance stability | ±0.05% / 100 Ω |
Power stability | ±0.025% / V |
Accuracy | |
Accuracy | ±0.1% of F.S. |
Temperature | |
Temperature drift | <±0.015% F.S. / °C |
Calibration temperature | 20 ... 28°C |
Response time | <250 ms |
Environmental | |
Medium | Air |
Operating Temp. | -20 ... 60°C |
Operating Humid. | 0 ... 95%RH(Non-condensing) |
Electrical | |
Power supply | DC 10 ... 30 V |
Protection | |
Pt100 signal disconnection protection & output | >23 mA |
Pt100 signal short circuit protection & output | <3 mA |
Output polarity protection | Yes |
IP rating | Housing : IP30 / Terminal : IP10 |
Certification | |
Certification | CE |
Material | |
Housing | ABS(UL94V-0) |
Applications
Monitoring for long-distance temperature signal transmission / For industries in heating / Ventilation / Air conditioning / Cooling / Water power / Electricity, etc. / For process in agriculture / Green house / Environmental engineering / Food / Pharmaceutical industry
Note : Design and specifications are subject to change without notice.
Note : Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.