PMM330 Differential Pressure Transmitter (Indoor)
Feature : Suitable for HVAC and light industry
Measuring element : Hot-wire type diff. pressure sensor, flow-through
Measuring range : ±50 ... ±1500 Pa
Output : 4 ... 20 mA / 0 ... 10 V / RS-485
Accuracy : ±1.0% F.S. ±4% M.V
IP rating : IP65
● Uses hot-wire type differential pressure sensor
● High sensitivity at low differential pressure, low zero-point drift, minimum measurable value as low as 1 Pa
● Pressure resistance up to 1 bar, differential pressure measurement range of ±50 ... ±1500 Pa
● Compact and easy to install
● Includes square root function for converting measurement into air velocity
● Provides analog output, optional RS-485 communication function
● DIP switch to adjust range and square root function
The eyc-tech PMM330 differential pressure transmitter is designed for small differential pressures and low air velocities. It uses a hot-wire type differential pressure sensor with excellent zero-point stability and the ability to detect small differential pressures, allowing for precise measurements at low air velocities. The built-in square root function is used for converting measurement in to air velocity, and it provides flexible output
options, making it an ideal choice for various differential pressure measurement applications.
Measurement | |
Measuring element | Hot-wire type diff. pressure sensor, flow-through |
Measuring range | ±50 ... ±1500 Pa |
Output | |
Output | 4 ... 20 mA / 0 ... 10 V / RS-485 |
Signal connection | 3-wire |
Load resistance | Current output : ≦ 500 Ω |
Response time | t63 ≦ 2 ms |
Display type | LCD Module with back light, double line character |
Display range | Upon request, 2 decimal place (as unit is Pa : 1 decimal place) |
Digit height | 5.56 mm |
Accuracy (at 25°C) | |
Accuracy | ±1.0% F.S. ±4% M.V. |
Temperature influence | 1% m.v. per 10°C |
Environment | |
Measuring medium | Air |
Operating temperature | 0 ... 50°C |
Operating humidity | 0 ... 95%RH (Non-condensing) |
Storage temperature | -20 ... +60°C |
Electrical | |
Power supply | DC 24 V ±10% & AC 24 V ±10% |
Current consumption | DC 24 V : ≦45 mA (Display) / ≦40 mA(Non-display) |
Overvoltage protection | ≦DC 40 V |
Electrical connection | M type ( M12 - 4 PIN connector ) / ( M12 - 5 PIN connector ) |
| *M type with 2 m cable | |
Installation | |
Installation | Indoor wall type |
Protection | |
IP rating | IP65 |
Electrical protection | ■ Over-voltage |
Pressure resistance | 1 bar |
Burst pressure | 3 bar |
Certification | |
Certification | CE |
Material | |
Housing | PC fire-proof class(PC-110)(UL94V-2) |
Weight | Display : 152 g |
Environmental monitoring (Clean rooms, HVAC) / Differential pressure monitoring (Air ducts, filters) / Airflow monitoring