PHM330 Differential Pressure Transmitter
Features : Suitable for industrial application. High pressure resistance.
Measuring element : Hot-wire type diff. pressure sensor, flow-through
Measuring range : ±50 ... ±1500 pa
Output : 4 ... 20 mA / 0 ... 10 V / RS-485
Accuracy : ±1.0% F.S. ±4% M.V
IP rating : IP65
PHM330 Differential Pressure Transmitter
Features : Suitable for industrial application. High pressure resistance.
Measuring element : Hot-wire type diff. pressure sensor, flow-through
Measuring range : ±50 ... ±1500 pa
Output : 4 ... 20 mA / 0 ... 10 V / RS-485
Accuracy : ±1.0% F.S. ±4% M.V
IP rating : IP65
Features
● Uses hot-wire type differential pressure sensor
● High sensitivity at low differential pressure, low zero-point drift, minimum measurable value as low as 1 Pa
● Pressure resistance up to 1 bar, differential pressure measurement range of ±50 ... ±1500 Pa
● Aluminum alloy housing, IP65 protection rating
● Includes square root function for converting into air velocity and airflow, and simultaneous display on the screen
● Provides analog output with RS-485 communication function
● DIP switch to adjust range and square root function
The eyc-tech PHM330 differential pressure transmitter, equipped with an aluminum alloy housing, is less affected by the external environment, ensuring stable and reliable airflow measurement. Its sensing element
is a hot-wire type sensor, providing excellent zero-point stability and the ability to detect low differential pressures, allowing for precise measurements at low air velocities.
Specification
Measurement | |
Measuring element | Hot-wire type diff. pressure sensor, flow-through |
Measuring range | ±50 ... ±1500 pa |
Output | |
Output | 4 ... 20 mA / 0 ... 10 V / RS-485 |
Signal connection | 3-wire |
Load resistance | Current output : ≦500 Ω |
Response time | t63 ≦ 2 ms |
Display type | LCD Module with back light, double line character |
Display range | V=Air velocity (at 25°C) |
Digit height | 5.56 mm |
Accuracy | |
Accuracy | ±1.0% F.S. ±4% M.V. |
Temperature influence | 1% m.v. per 10°C |
Environment | |
Measuring medium | Air |
Operating temperature | -20 ... +80°C (Non-display) |
Operating humidity | 0 ... 95%RH (Non-condensing) |
Storage temperature | -20 ... +80°C |
Electrical | |
Power supply | DC 24 V ± 10 % & AC 24 V ± 10 % |
Current consumption | DC 24 V : ≦45 mA(Display) / ≦40 mA(Non-display) |
Overvoltage protection | ≦DC 40 V |
Electrical connection | M12 connector |
Installation | |
Installation | Wall |
Protection | |
IP rating | IP65 |
Electrical protection | ■ Over-voltage |
Pressure resistance | 1 bar |
Burst pressure | 3 bar |
Certification | |
Certification | CE |
Material | |
Housing | Aluminum alloy |
Weight | Display : 497 g |
Applications
Exhaust air treatment / Differential pressure monitoring / Airflow monitoring / Water treatment / Air handling unit flow