FTC06 Temperature and Flow Transmitter
Features : Thermal mass measurement of flow and temperature with RS-485, ideal for continuous liquid cooling monitoring in data centers.
Sensor type : PT sensor
Measuring range : 0 ... 3 m/s (Water), 0 ... 60 m/s (Air)
Output : 4 ... 20 mA / RS-485 / NPN
Repeatability : ±0.5%
Accuracy : Water ±(1% mv + 0.05 m/s), Air ±(1% mv + 0.5 m/s)
IP rating : IP65, IP67 (Option)
FTC06 Temperature and Flow Transmitter
Features : Thermal mass measurement of flow and temperature with RS-485, ideal for continuous liquid cooling monitoring in data centers.
Sensor type : PT sensor
Measuring range : 0 ... 3 m/s (Water), 0 ... 60 m/s (Air)
Output : 4 ... 20 mA / RS-485 / NPN
Repeatability : ±0.5%
Accuracy : Water ±(1% mv + 0.05 m/s), Air ±(1% mv + 0.5 m/s)
IP rating : IP65, IP67 (Option)
● Rugged aluminum housing for harsh environments.
● Thermal mass measurement with fast response and low pressure loss.
● RS-485 output for real-time flow and temperature.
● Works with eyc-tech DPM04 for instantaneous and totalized flow display.
● Tracks flow changes for early anomaly detection and preventive maintenance.
● Optimizes cooling efficiency and supports ESG energy savings.
● One-piece probe design for stable long-term liquid cooling measurement.
Input | |
Input | PT sensor |
Measuring range | 0 ... 3 m/s (Water) |
Output | |
Output | 4 ... 20 mA / RS-485 / NPN |
Load resistance | Current output:≦500 Ω |
Response time (at +25°C) | t90 <10 sec |
Filter response | 0 ... 100 adjustable |
Sampling time | 1 cycle/sec |
Accuracy (at +25 °C) | |
Repeatability | ±0.5% |
| Water flow | 0 ... 1 m/s:±( 1% of mv. + 0.05 m/s ) 1 ... 2 m/s:±( 2% of mv. + 0.2 m/s ) 2 ... 3 m/s:±( 3% of mv. + 0.3 m/s ) |
| Air flow | 0 ... 30 m/s:±( 1% of mv. + 0.5 m/s ) 30 ... 60 m/s:±( 1.5% of mv. + 1 m/s ) |
| Temperature | ±0.5% of F.S |
Temperature drift | ≦0.5% F.S. / °C |
| Installation angle effect | <1.5 % mv for α <10° |
| Uncertainty of factory calibration | ±1% |
| *The measurement range is defined at the standard condition(1013 mbar, 25°C). *mv = measured value *At an air velocity of 0 m/s, self-heating of the probe may affect the temperature reading in air. Therefore, the measured value may not represent the actual ambient temperature. *CAUTION: The probe may become hot during operation. To prevent burns, do not touch theprobe directly. | |
Communication | |
Comm. Interface & Protocol | RS-485 Modbus RTU |
RS-485 Baud Rate | 9600、19200、38400、57600、115200 bps |
Electrical | |
Power supply | DC 24 V ±10% |
Current consumption | < 120 mA |
Electrical connector | M12 8P connector |
Environmental | |
Medium | Liquid, air |
Operating Temp. (Housing) | -20 ... +60°C |
Operating Humid. (Housing) | 0 ... 90% (Non-condensing) |
Probe Operating Temp. | 0 ... 50°C |
Storage temperature | -25 ... +60°C |
Probe pressure resistance | 16 bar |
Installation | |
Installation | 1/4″G or 1/2″G thread |
Certification | |
Certification | CE |
Protection | |
IP rating | IP65 (Housing), IP67 (Option) |
Electrical protection | ■ Reverse polarity ■ Over-voltage |
Material | |
Housing | Aluminum alloy |
Probe | 316L |
Weight | 1/4″G thread : 85 g |
AI Servers / Precision Manufacturing / Data Centers / Semiconductor / Electronics / Chemical / Pharmaceutical / Steel industry / Biotechnology / Industrial process monitoring / Air conditioning / Cleanroom / Laboratory / Weather station / Hospital / Buildings / Dryers / Factories / Storage rooms / Environmental ventilation control / Environmental test chambers / Greenhouses