FDM09-I Venturi Thermal Mass Flow Meter (Liquid / Air)

Feature: Bypass Venturi flow path design with high sensitivity, low pressure loss, and stable repeatability, supporting simultaneous flow and liquid temperature measurement
Sensor Type: Hot-wire sensor
Turndown Ratio: 50 : 1
Measuring Range: DN15: 42 L/min, DN25: 150 L/min, DN32: 250 L/min, DN40: 380 L/min, DN50: 600 L/min
Output: 4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Accuracy: ±1% F.S.
IP Rating: IP65

FDM09-I Venturi Thermal Mass Flow Meter (Liquid / Air)

Feature: Bypass Venturi flow path design with high sensitivity, low pressure loss, and stable repeatability, supporting simultaneous flow and liquid temperature measurement
Sensor Type: Hot-wire sensor
Turndown Ratio: 50 : 1
Measuring Range: DN15: 42 L/min, DN25: 150 L/min, DN32: 250 L/min, DN40: 380 L/min, DN50: 600 L/min
Output: 4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Accuracy: ±1% F.S.
IP Rating: IP65


High Sensitivity : Detects minor flow changes for early identification of blockage, leakage, or circulation issues.
Bypass Design : Directs part of the main flow through a thermal sensing path for sensitive measurement.
Low Pressure Loss : Venturi flow path drives bypass flow while supporting pressure recovery.
Stable Repeatability : Fixed flow path design maintains a consistent flow-split ratio.
No Conductivity Limitation : Suitable for water, DI water, and selected coolants with proper calibration.
Flow & Temperature Measurement : Supports cooling-capacity and energy calculations using flow and supply/return temperature difference.


Input

Sensor Type
Hot-wire sensor
Turndown Ratio
50 : 1
Measuring Range*
DN15 : 42 L/min
DN25 : 150 L/min
DN32 : 250 L/min
DN40 : 380 L/min
DN50 : 600 L/min
*The measurement range is defined at the standard condition (1013 mbar, 25°C).

Output

Output Signal
4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Signal Connection
M12 8pin 3-wire output
Warm-up Time
60 sec
Response Time
t90≦6 sec
Load Resistance
Current output : ≦500 Ω
Voltage output : ≧10 KΩ

Communication

Communication Methods & Protocol
RS-485 Modbus RTU
RS-485 Baud Rate
9600, 19200, 38400, 57600, 115200 bps

Accuracy ( at 25°C )

Accuracy
±1% F.S.
Temp. Influence
0.05% / °C
Reproducibility
0.5% F.S.

Environmental

Medium
0 ... 80°C, Non-corrosive liquid
Operating Temp. & Humid.
0 ... 60°C / 20 ... 90%RH (Non-condensing)
Storage Temp.
-20 ... +60°C
Operating Pressure
16 bar

Electrical

Power Supply
DC 24 V ±10%
Current Consumption
24 V : 110 mA
Relay Capacity
Max current : 6 A
Max voltage : DC 24 V (DC 36 V Max)
Electrical Connection
M12 8P connector

Installation

Pipe Connection
G thread
Pipe Size
DN15 ( 1/2″ )
DN25 ( 1″ )
DN32 ( 1-1/4″ )
DN40 ( 1-1/2″ )
DN50 ( 2″ )

Display

Display Readout
0 ... 99999999 (Cumulative flow : 8-digit)
0 ... 99999 (Instantaneous flow : 5-digit)
Decimal Point
Button
Sampling Time
1 cycle/sec
Flow Unit
mL, L, m³, gal, ft³, inch³, UK gal
Time Unit
/min, /hr
Response Time Adjustment Range
0.5 ... 300 sec

Certification

Certification
CE

Protection

IP Rating
IP65
Electrical Protection
■ Reverse polarity ■ Over-voltage

Material

Pipe
Aluminum alloy / Stainless steel / POM
Housing
Aluminum alloy
Weight
DN15 ( 1/2″ ) : 0.8 Kg
DN25 ( 1″ ) : 0.8 Kg
DN32 ( 1-1/4″ ) : 0.9 Kg
DN40 ( 1-1/2″ ) : 1.1 Kg
DN50 ( 2″ ) : 1.3 Kg

 


AI Data Center Liquid Cooling / CDU Coolant Supply and Return Flow Measurement / Rack Manifold Flow Measurement / Cold Plate Water Circulation Flow Measurement / Server and GPU Liquid Cooling Circulation Systems / Semiconductor Equipment Cooling Water Flow Measurement / Cooling Circulation Systems / Industrial Equipment Cooling Water and Non-corrosive Liquid Flow Measurement

Note : Design and specifications are subject to change without notice.
Note : Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.