FDM06-X Thermal Mass Diff. Pressure Signal Processor
High-accuracy thermal mass differential pressure sensor with K-factor correction, real-time display, versatile outputs, and compatibility with various elements.
Sensor type : Hot-wire sensor
Turndown ratio : 100 : 1
Output : 4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Accuracy : 60 m/s:±(1.5% F.S.)
IP rating : IP65
FDM06-X Thermal Mass Diff. Pressure Signal Processor
High-accuracy thermal mass differential pressure sensor with K-factor correction, real-time display, versatile outputs, and compatibility with various elements.
Sensor type : Hot-wire sensor
Turndown ratio : 100 : 1
Output : 4 ... 20 mA / 0 ... 10 V / Relay / RS-485
Accuracy : 60 m/s:±(1.5% F.S.)
IP rating : IP65
● Thermal mass differential pressure principle:
High accuracy ±1.5% F.S., without the need for temperature or pressure compensation
● Turndown ratio 100:1 with high sensitivity design:
Superior to conventional differential pressure sensors in detecting subtle airflow variations
● On-site K-factor correction:
Simple calculation allows input of the corresponding K-factor to align measurements with true values
● Real-time display & system integration:
Capable of showing flow velocity/flow rate, and with eyc-tech DPM03 / DPM04 enables full-range linearization and totalizing flow calculation
● Versatile outputs:
Supports Analog / Relay / RS-485, making system integration flexible and convenient
● Easy installation:
Ferrule fittings for flexible or rigid tubing.
● High compatibility:
Applicable to a wide range of differential pressure elements (Pitot tube, averaging tube, Annubar, Venturi, orifice plate, V-cone, etc.)
Input | |
Sensor type | Hot-wire sensor |
Turndown ratio | 100 : 1 |
Measuring range | Max. 60 m/s |
Output | |
Output signal | 4 ... 20 mA / 0 ... 10 V / Relay / RS-485 |
Signal connection | 3-wire |
Warm-up time | 60 sec |
Response time | t90≦6 sec |
Load resistance | Current output : ≦500 Ω |
Communication | |
Communication methods & protocol | RS-485 Modbus RTU |
RS-485 baud rate | 9600、19200、38400、57600、115200 bps |
Accuracy | |
Accuracy | 60 m/s:±(1.5% F.S.) |
Temp. influence | 0.2% / °C |
Uncertainty of factory calibration | ±1% |
*The measurement range is defined at the standard condition(1013 mbar, 20°C). *Accuracy based on tests with a 300 mm averaging Pitot tube. | |
Environmental | |
Medium | Non-corrosion gas / Air |
Operating Temp. | 0 ... 50°C / 20 ... 90%RH (Non-condensing) |
Operating Humidity | 20 ... 90%RH(Non-condensing) |
Storage Temp. | -20 ... +60°C |
Body operating pressure | 16 bar |
Electrical | |
Power supply | DC 24 V ±10% |
Current consumption | 24 V : 110 mA |
Relay capacity | Max current : 6 A |
Electrical connection | M12 8P connector |
Installation | |
Installation | Ferrule fittings:1/4″(Rigid), Ø6(Flexible) |
Display | |
Display readout | 0 ... 99999999 (Cumulative flow : 8-digit) |
Decimal point | Button |
Sampling time | 1 cycle/sec |
Flow unit | m/s, ft/s, L/min, m³/min, m³/h, mL, L |
Response time adjustment range | 0.5 ... 300 sec |
Certification | |
Certification | CE |
Protection | |
IP rating | IP65(Housing) |
Electrical protection | ■ Reverse polarity ■ Over-voltage |
Material | |
Housing | Aluminum alloy |
Industrial compressed air & energy management:Zonal consumption monitoring, leakage detection, energy metering
Process gases & supply control:Flow billing, mixing ratio monitoring, high-pressure/high-velocity flow monitoring
HVAC & cleanroom:Duct flow monitoring, laminar flow, positive/negative pressure, environmental control
Biotech & pharmaceutical:Aseptic area and gas supply stability monitoring
Environmental monitoring & ESG:Emission measurement, CO2 equivalent conversion, ESG energy statistics