AFMC HVAC Average Flow Measuring Tube
Features : Multi-hole averaging design for stable HVAC duct measurement down to 1 m/s with the PMM330.
Operating pressure : 1 bar
Operating temperature : 0 ... 80°C
Length : 100 ... 1000 mm
Features
● Pitot tube : Measure differential pressure caused by flow, combined with differential pressure sensor to calculate flow.
● Multi-Hole Structure : Averages differential pressure readings from multiple points for stable and reliable measurements.
● High Sensitivity : Low pressure drop within the tube enables measurement of small value.
● Durable Material : Aluminum tube for easy installation and stable performance in HVAC environments.
● Low Air Velocity Measurement : Paired with eyc-tech PMM330 to measure air velocity down to 1 m/s.
● Dust-Resistant : Features a dust-resistant structure that resists clogging, ensuring stable flow measurement.
AFMC adapts the Pitot tube principle, where the combination of the Pitot tube and a differential pressure sensor is commonly used for flow measurement. It measures the differential pressure between the total pressure and static pressure of the fluid, allowing for the calculation of fluid velocity. The difference between total and static pressure is known as dynamic pressure, which results from fluid flow and is proportional to the square of the flow velocity. By measuring dynamic pressure, the fluid speed can be accurately determined.
The AFMC averaging Pitot tube features a multi-hole structure, which averages pressures from multiple points to better represent the actual flow profile within the pipe, ensuring stable and precise measurements.
Specification
Environment | |
Operating pressure | 1 bar |
Operating temperature | 0 ... 80°C |
Measuring medium | Air |
Flow coefficient (K) | 0.82 ... 0.84 |
Installation | |
Installation | Insertion type (Please install vertically.) |
Connection | |
Installation connection | Secure with screws. |
Outlet connection | 1/8″ thread |
Material | |
Measuring tube | Aluminum Extruded Tube |
Connection | SS304 Stainless Steel |
Applications
HVAC system / Ventilation ducts / Low flow measurement