• eYc FTM06 Hot wire thermal air velocity transmitter
  • eYc FTM06 Hot wire thermal air velocity transmitter

eYc FTM06 Hot wire thermal air velocity transmitter

Feature:Micro-corrosion air measurement. Strong housing with analog and RS-485 output.
Type:Resistance temperature detector
Range:Air:0 ... 60 m/s
Output Signa:Analog:4 ... 20 mA / 0 ... 10 V ; RS-485
Product Accuracy:Air(at 25°C):3%<60 m/s(Because the probe is affected by the operating Temp., there will be some error)
Power Supply:8 ... 35 VDC
●Additional option (ILAC/TAF) Test report - Standard calibration laboratory (TAF accreditation:3032, using ISO/IEC 17025)
Model : eYc FTM06

Micro-corrosion air measurement. 
Strong housing with analog and RS-485 output.

FTM06 is based on thermodynamic principle,  there are 2 temperature sensors inside the probe: one for  temperature measurement, the other one as a measuring conveyor after  heated. 
Temperature difference between the two as a basis for measuring flow rate. When the medium flow rate increases, the temperature difference decreases. 
The temperature difference converted to standard signal output after processed that is why flow rate can be measured by these two sensors. All-metal housing, suitable for a variety of pipe diameters.

  • Type:Resistance temperature detector (RTD)
  • Range:Air : 0 ... 60 m/s
  • Output signal:Analog : 4 ... 20mA / 0 ... 10V;RS-485
  • Product accuracy:Air(at 25°C):3%<60 m/s(Because the probe is affected by the operating Temp., there will be some error)
  • Response time:t90>90 s
  • Medium:Water and gas which is compatible with stainless steel
  • Power supply:8 ... 35 VDC
  • Installation:Metal flange mount or metal quick connector
  • Protection:IP67
  • Material:Housing SUS304

The specifications contained herein are subject to change without notice and any user of said specifications should verify from the manufacturer that the specifications are currently in effect. Otherwise, the manufacturer assumes no responsibility for the use of specifications which may have been changed and are no longer in effect.

*Please make sure the product and the device which connect with RS-485 are on common ground, avoid damaged product.

  • IP67
  • Resistance Temperature Detector
  • Analog and RS-485 output
  • Applicable micro corrosion air
  • Strong stainless steel housing, for a variety of harsh environments
  • Built-in with temperature compensation, accommodate quickly any environment
  • Industrial process gas supply, consumption and dry flow monitoring
  • Compressed air consumption measurement Buildings, Factories, Clean rooms, Hospitals, Semiconductors, Electronics, Paper, Printing, Textiles, Steel, Food, Chemicals, Pharmaceuticals, Biotechnology industries