Display

View:

eYc THS30X Series Multifunction Temperature & Humidity Transmitter (indoor/duct/remote/outdoor)

Features : Multifunction physical quantities ─
temperature & humidity / dew point / frost point /
wet-bulb temp. / vapor pressure /mixture ratio /
absolute humidity / specific enthalpy
Input : Capacitive Humidity Sensor & PT 100Ω class A
Output : standard RS-485 or 2 analog output
( 0 ... 20 mA / 4 ... 20mA / 0 ... 1V / 0 ... 5V / 0 ... 10V )
Linear Accuracy (at 25°C) :
temperature ± 0.2 °C ± 0.005 °C x t actua /
humidity ( at + 25 °C ) ± 2 %RH
Working Range Suggestion :
temperature 0 ... 50 °C ( THS301 );
- 40 ... + 80 °C ( THS302 / S304 / 307 ) /
humidity : 0 ... 100 %RH / dew point - 40 ... + 60 °C /
Other please refer to physical quantity measuring range list
Display:Optional
●Additional option (ILAC/TAF) Test report - Standard Calibration laboratory(TAF Accreditation: 3032)

eYc DPT02 Signal Converter

Features:Local display, easy keypad programming the signal output and scale, led for working status.
Accuracy : 0.2 % F.S. ± 1 digital
Sampling time : 4 cycle / sec
Response time adjustment range : 0.5 ... 60 sec
Input : voltage : 0 ... 5V ; 0 ... 10V ; Current : 0 ... 20mA ; 4 ... 20mA ; RTD : Pt100 / Pt1000, 2/3w
Output : voltage : 0 ... 5V ; 0 ... 10V ; Current : 0 ... 20mA ; 4 ... 20mA
Output signal : analog output / RELAY /RS-485

eYc DPM02 Multifunction Signal Display Monitor

eYc GS23 CO2 Transmitter / Indoor type

Input :Data can be logged and transferred to pc via RS-485 function link free software. 1 analog output or Modbus RS-485. Optional LCD display.
Input : NDIR sensor
Output : 0 ... 5 V / 0 ... 10 V / 4 ... 20 mA
Accuracy ( at +25 °C ;101.3 kPa ) : ± 40 PPM ± 3 % of reading
Measuring Range : 0 ... 2000 PPM
Display : Optional
●Additional option (ILAC/TAF) Test report - Standard Calibration laboratory(TAF Accreditation: 3032)

eYc PMD33 Differential Pressure Transmitter

Feature :
Input : Piezoelectric Differential Pressure Module
Output : 0 ... 20mA / 4 ... 20mA / 0 ... 5V / 0 ... 10V
Range : ± 50 ... ± 2500 pa
Accuracy : ± 2.0 % of F.S.
Display : Optional

eYc THM06 Industrial high temperature multi-function dew point transmitter 【Preliminary】

Feature : Adaptation to high temperature and high humidity conditions or harsh environments such as chemical pollution & condensation
Input : ​Capacitive humidity sensor & Pt100Ω
Measurement range : ​-40 ... +120°C ;
Customized up to 150°C (optional) ;
0 ... 100%RH (non-cond.) ; -60 ... +60dp°C
Output: ​4 ... 20mA / 0 ... 10V / RS-485
Signal connection : 3-wire
Accuracy :±0.15°C+0.002°C x t actual ;
0 ... 100%RH (non-cond.) ; ±3dp°C ± (0.02%F.S./°C)